Xw60ls Manual: Dixell

If configured as dor (door switch): opening the door stops fans and displays dA after a delay (parameter doA ). Closing the door restarts normal operation. The XW60LS flashes an alarm code on the display while the red LED blinks.

| i1P | Function | |-------|-----------| | oP | Door switch – normal open | | cL | Door switch – normal closed | | EAL | External alarm (generic) | | bAL | Serious alarm (compressor stop) | | PAL | Pressure switch alarm | | dor | Door switch with fan cut-off and defrost inhibition | dixell xw60ls manual

For specific OEM variations (e.g., XW60LS with different probe curves or custom passwords), consult the original equipment manufacturer’s supplement. Refer to Emerson/Copeland’s official XW60LS – ISTR 03/11 installation manual or contact technical support with the controller’s full model code and firmware version (visible during power-up). If configured as dor (door switch): opening the